Digital Controllers Fan Coil & Line Voltage thermostats by PECO
Standalone digital thermostats that handle line or low voltage control of heat, cool, outside air and up to 3 fan speeds with 2/4 pipe configuration.
T180
- Programmable
- 7-day / 4-event
- 3 Fan speeds w/ setback capability
- 24 or 110-277 VAC supply voltage selection
- Key pad lockout
- 2-pipe/4-pipe fan coil configuration
- Manual or auto changeover
- Remote sensor, occupancy setback ready
- LCD display with backlight
- Fahrenheit or Celsius display
- Energy Star, ASHRAE 90.1 & Title 24 compliant
T170
- Non-programmable
- 3 Fan speeds w/ setback capability
- 24 or 110-277 VAC supply voltage selection
- Keypad lockout
- 2-pipe/4-pipe fan coil configuration
- Manual or auto changeover
- Remote sensor, occupancy setback ready
- LCD display with backlight
- Fahrenheit or Celsius display
- ASHRAE 90.1 & Title 24 compliant
Specifications
Temperature Control Range | 50 to 90°F / 10 to 32°C factory default, adjustable inward |
Maximum Ambient | 130°F / 54°C |
Load Connections | Wire leads |
Agency Approvals | UL, UL Canada |
Physical Dimensions | 5.8” W x 4.4" H x 1.4" D 14.7 cm x 11.2 cm x 3.6 cm |
Mounting | Installs on standard 4" x 4" (10.2 cm x 10.2 cm) device box with 2" x 4" (5.1 cm x 10.2 cm) horizontal mud ring |
Technical Data
Ratings
VOLTAGE | FLA | LRA | RES AMPS | PILOT DUTY | HP |
24 VAC | NA | NA | NA | 24 VA | NA |
120 VAC | 5.8 | 34.8 | 6.0 | 125 VA | 1/4 |
240 VAC | 2.9 | 17.4 | 5.0 | 125 VA | 1/4 |
277 VAC | 2.4 | 14.4 | 4.2 | 125 VA | 1/4 |
Models & Accessories
Model | Part No. | Description |
TA170-001 | 68348 | Non-programmable. 1H/1C, up to 3 fan speeds. |
TB170-001 | 68457 | Non-programmable. 1H/1C, up to 3 staged fan speeds |
TA180-001 | 69378 | Programmable. 1H/1C, up to 3 fan speeds. |
TB180-001 | 69379 | Programmable. 1H/1C, up to 3 staged fan speeds. |
69308 | 69308 | Remote wall sensor |
68671 | 68671 | Remote probe, pipe sensor |
SB200-001 | 68375 | Occupancy sensor - time based |
SK200-001 | 68381 | Occupancy sensor - guest room |