KMC CONTROLS MEP-4200/4500/4900 Series Fail-Safe, Direct-Coupled, Actuators (25/45/90 in-lb.)
Description and Application These compact but powerful direct-coupled ControlSet® actuators provide two-position, tri-state, or
proportional control for dampers or valves in HVAC
systems. Efficient, durable, capacitor-driven fail-safe
with switch-selectable direction provides consistent torque in both powered and fail-safe modes.
A patented noise reducer provides whisper-quiet
operation in both modes. A minimum torque of 25
(MEP-42xx), 45 (MEP-45xx), or 90 (MEP-49xx) in-lb.
is availa
…
2024 Apr 16th
Sizing/Selecting – Water Valve Application
Pressure
Dependent Valves
1)What type of valve would the customer like?Ball Valve
(CCV, ZoneTight, Industrial), Globe Valve or Butterfly Valve
2)Calculating the CV.What is CV?
CV = The amount of water flow (GPM) through a fully open
valve with 1 psi pressure drop.Why is CV
important?If CV is too
high, that means the valve is oversized and this will result in sloppy control
and inefficient system performance.If CV is too
low, that could result in insufficient flow and starve the coil. Y
…
2024 Mar 25th
Sizing/Selecting A Damper Actuator
The Belimo 10 Step process for sizing and selecting a damper
actuator:1)What is the Area of the damper?We need to find the height and width of the damper. The
customer may provide this in millimetres (mm). If so, multiply the millimeters
by 0.039 to convert it into inches. Once in Inches, multiply the height and
width and divide by 144 to get the area in square ft (sq. ft). If the customer
provides it is Feet (ft), no need to convert it to inches. The height and width
can just be multiplie
…
2024 Mar 25th