Blog
RIB Relay & DC Power Packs
RIB POWER PACKS are designed to provide low voltage power to the ever-increasing sensor systems of today’s building automation systems. With an on-board 20 Amp rated relay, RIB POWER PACKS come ready to switch line voltage to your load when the low voltage control signal is received. Check out some of the features!
On-board 20 Amp rated SPDT relayRequires input power anywhere between 120-277Vac24Vdc, Class 2 rated outputModel RIB21BPP5 (5W) provides up to 210mA @ 24VdcModel RIB21BPP10 (10W) pro
…
2024 Apr 23rd
BAC-5051AE | ROUTER: BACNET, IP / DUAL ENET / SINGLE MSTP
DESCRIPTION
The KMC Controls BAC-5051AE is a multi-port BACnet router. It
is powerful enough for heavy network traffic and small enough
to use as a control technician’s service tool. Routing Install the BAC-5051AE for BACnet IP, Ethernet, and
MS/TP routing. IP routing is fully compliant with BACnet
Standard 134-2012, Annex J. Browser Configuration Configure the BAC-5051AE using only an
Internet browser. There is no special software to learn or load. Flexible Mounting Two mou
…
2024 Apr 10th
Single and Dual Duct VAV Controllers SimplyVAV
Description The SimplyVAV series of controllers are an easy and
unique approach to operating a wide variety of VAV
terminal units. The integrated actuators, internal
airflow sensors, and wide variety of application
programs make these BACnet Application
Specific Controllers ideal for either new or retrofit
installations. Easy to install Just mount the controller, wire it
to a 24 volt transformer, and then connect airflow
and temperature sensors. A SimplyVAV controller
automati
…
2024 Apr 9th
Sizing/Selecting – Water Valve Application
Pressure
Dependent Valves
1)What type of valve would the customer like?Ball Valve
(CCV, ZoneTight, Industrial), Globe Valve or Butterfly Valve
2)Calculating the CV.What is CV?
CV = The amount of water flow (GPM) through a fully open
valve with 1 psi pressure drop.Why is CV
important?If CV is too
high, that means the valve is oversized and this will result in sloppy control
and inefficient system performance.If CV is too
low, that could result in insufficient flow and starve the coil. Y
…
2024 Mar 25th
Sizing/Selecting A Damper Actuator
The Belimo 10 Step process for sizing and selecting a damper
actuator:1)What is the Area of the damper?We need to find the height and width of the damper. The
customer may provide this in millimetres (mm). If so, multiply the millimeters
by 0.039 to convert it into inches. Once in Inches, multiply the height and
width and divide by 144 to get the area in square ft (sq. ft). If the customer
provides it is Feet (ft), no need to convert it to inches. The height and width
can just be multiplie
…
2024 Mar 25th