Duct Averaging Temperature SensorFEATURES Galvanized enclosure with Quick Attach Cover Flexibale Lengths of 8’, 12’, 24’ or Rigid Probe Length of 18” Patented Quick Coupling from enclosure to sensing tube Quick Connect wire terminals eliminate wire nuts NTC thermistor, RTD elements and transmitters available Compatible with most major control systems CE & RoHS compliant 5 Year Limited Warranty Made in USA GENERAL INFORMATION High
…
2024 Apr 10th
Sizing/Selecting – Water Valve Application
Pressure
Dependent Valves
1)What type of valve would the customer like?Ball Valve
(CCV, ZoneTight, Industrial), Globe Valve or Butterfly Valve
2)Calculating the CV.What is CV?
CV = The amount of water flow (GPM) through a fully open
valve with 1 psi pressure drop.Why is CV
important?If CV is too
high, that means the valve is oversized and this will result in sloppy control
and inefficient system performance.If CV is too
low, that could result in insufficient flow and starve the coil. Y
…
2024 Mar 25th
Sizing/Selecting A Damper Actuator
The Belimo 10 Step process for sizing and selecting a damper
actuator:1)What is the Area of the damper?We need to find the height and width of the damper. The
customer may provide this in millimetres (mm). If so, multiply the millimeters
by 0.039 to convert it into inches. Once in Inches, multiply the height and
width and divide by 144 to get the area in square ft (sq. ft). If the customer
provides it is Feet (ft), no need to convert it to inches. The height and width
can just be multiplie
…